    Mode: { AUTOMATIC: 2; AWAY: 1; HOME: 0 } = ...

    Basic ventilation mode: Home (0), Away (1), or Automatic (2) — the unit dynamically adjusts fan speed itself rather than following a fixed per-mode setting. Automatic was added in unit firmware 3.1.4; reverse- engineered from a live unit's WebSocket traffic (STATE register write of 2), since neither the Modbus RTU manual nor the firmware changelog document its register encoding.

    Type Declaration

    • ReadonlyAUTOMATIC: 2
    • ReadonlyAWAY: 1
    • ReadonlyHOME: 0